| Fiber Type |
OS2 |
| Fiber Grade (Acc. to ITU-T) |
G.652D & G.657A1 |
| Fiber Count |
12 |
| Fiber Color Coding |
TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua |
| Number of Active Subunits |
1 |
| Fibers Per Subunit |
12 |
| Subunit Waterblocking |
Gel Filled |
| Subunit Diameter |
3.3 mm |
| Subunit Color |
TIA coding (Gxxxxxx.T): Natural |
| Cable Core Water Blocking |
Waterblocking Glass Yarns |
| Jacket Material |
PE - Polyethylene |
| Nominal Diameter |
5.8 mm (0.23 in) |
| Optical Characteristics |
| Wavelength |
1310 nm / 1550 nm / 1625 nm |
| Max. Attenuation |
0.39 dB/km / 0.24 dB/km / 0.29 dB/km |
| Mechanical Tests |
| Min. Bend Radius (Installation) |
116 mm (IEC 60794-1-21-E6) |
| Min. Bend Radius (Operation) |
58 mm (IEC 60794-1-21-E11) |
| Max. Tensile Strength (Installation) |
1500 N (IEC 60794-1-21-E1) |
| Max. Tensile Strength (Operation) |
500 N (IEC 60794-1-21-E1) |
| Max. Crush Resistance (Installation) |
15 kN/m (IEC 60794-1-21-E3) |
| Max. Crush Resistance (Operation) |
7.5 kN/m (IEC 60794-1-21-E3) |
| Bulk Cable Weight |
28 kg/km (19 lbs/1000 ft) |
| Installation Temperature Range |
-5 C to +50 C |
| Operating Temperature Range |
-40 C to +75 C |
| Storage Temperature Range |
-40 C to +75 C |
| Environmental Suitability |
Outdoor |
| ISO/IEC Compliance |
IEC 60794, ISO/IEC 11801-1 |