Main |
Product or Component Type |
Uninterruptible Power Supply (UPS) |
Runtime for Load |
270–2700W (6 min 15 s at full load) |
Max Capacity Used |
100% |
Batteries & Runtime |
Battery Type |
Lead-Acid battery |
Extendable Runtime |
Yes (1 pack supported) |
Included Battery Modules |
0 |
Battery Slots Empty |
0 |
Typical Recharge Time |
3 hours |
RBC Quantity |
1 |
Battery Life |
3–5 years |
Replacement Battery |
APCRBC143 |
Battery Charge Power |
245 W rated |
General |
Provided Equipment |
CD with software, Rack Mounting rails, RS-232 cable, Temperature probe, User Manual, Web/SNMP Card |
Redundant |
No |
Physical |
Rack Units |
4U |
Color |
Black |
Dimensions (H x W x D) |
17.008 in x 7.008 in x 19.02 in |
Mounting |
Rack-mounted (Front, Lower, Two-post mountable) |
USB Compatible |
Yes |
Cable Length |
8 ft (2.4 m) |
Input |
Main Input Voltage |
208 V / 230 V |
Other Input Voltages |
220 V / 240 V |
Input Frequency |
50/60 Hz + 3 Hz (Auto-sensing) |
Input Voltage Range |
140–280 V |
Input Connection Type |
BS1363A, IEC 320 C20, Schuko (CEE 7 / EU1-16P) |
Output |
Rated Power |
2700 W / 3000 VA |
Max Configurable Power |
2700 W / 3000 VA |
Main Output Voltage |
230 V |
Other Output Voltages |
208 V, 220 V, 240 V |
Output Frequency |
50/60 Hz + 3 Hz sync to mains |
Output Connections |
8 x IEC 320 C13, 2 x IEC Jumpers, 2 x IEC 320 C19 |
Harmonic Distortion |
< 5% |
Transfer Time |
6 ms typical, 10 ms max |
Topology |
Line Interactive |
Waveform Type |
Sine wave |
Conformance |
Certifications |
CE, CSA, C-tick, EAC, GOST, IRAM, VDE, UK PSTI |
Standards |
EN/IEC 62040-1:2019/A11:2021, EN/IEC 62040-2:2006/AC:2006, EN/IEC 62040-2:2018 |
Environmental |
Acoustic Level |
55 dBA |
Heat Dissipation |
184 BTU/h |
Operating Temp |
32–104 F (0–40 C) |
Storage Temp |
5–113 F (-15–45 C) |
Operating Altitude |
0–10,000 ft |
Storage Altitude |
0–50,000 ft |
Relative Humidity |
0–95% (Operating & Storage) |
Communications & Management |
Control Panel |
Multi-function LCD + LED indicators |
Emergency Power Off (EPO) |
Yes |
Pre-Installed Cards |
Network management card 3 with environmental monitoring |
Alarms |
On battery, Low battery, Overload (with configurable delays) |
Surge Protection & Filtering |
Surge Energy Rating |
645 J |
Filtering |
Full-time multi-pole filtering: 0.3% surge let-through, zero clamping time |